Standard
Rating : 0.8-10 AMPERE
Input Power : 125 VAC / 250 VAC / 12 VDC /24 VDC
Dielectric Strength
: 1500VAC / 1 Minute.
Interrupt Capacity
: 125 VAC x 1000A
Insulation Resistance : >100 M¢G[
Calibration :
25°C-100%
of Rated Current-Continuously Carried.
25°C-Between
101% to 149%-May Trip or Not.
25°C-150% of
Rated Current-Trip Within 1 HR.
25°C-200% of
Rated Current-Trip Within 2-50 Sec
25°C-300% of
Rated Current-Trip Within 0.5-5 Sec
25°C-400% of
Rated Current-Trip Within 0.3-1 Sec
25°C-500% of
Rated Current-Trip Within 0.2-0.7 Sec 25°C-600%
of Rated Current-Trip Within 0.1-0.5 Sec
Contact Endurance : 125 VAC x 200% of Rated Current
-500 Cycles.
Reset Method:Auto Reset.
Maximum Internal Resistance
|
Amp
|
Ohm
|
|
|
0.8A-1.5A
|
0.150
|
|
|
1.5A-2A
|
0.120
|
|
|
2A-3A
|
0.075
|
|
|
3A-4A
|
0.050
|
|
|
4A-5A
|
0.050
|
|
|
5A-6A
|
0.035
|
|
|
6A-7A
|
0.035
|
|
|
7A-8A
|
0.035
|
|
|
8A-9A
|
0.030
|
|
|
9A-10A
|
0.030
|
|
|