Reset
: Manual Push Reset.
Standard Rating : 3-20 AMPERE
Input Power : 125 /
250 VAC
Dielectric Strength : 1500VAC / 1 Minute.
Interrupt Capacity : 125 VAC x 1000A, 250
VAC x 1000A.
Insulation Resistance
: >100 MOhm
Calibration :
25°C
- 105% of Rated Current - Continuously Carried.
25°C
- Between 101% to 145%-May Trip or Not.
25°C-
150% of Rated Current -Trip Within 1Hour.
25°C-
200% of Rated Current -Trip Within 1Minute.
Contact Endurance : 125 VAC*150% of Rated
Current -500 Cycles.
Approval:
3-15A 125 / 250VAC
Maximum Internal Resistance
|
Amp
|
Ohm
|
|
|
3A-4A
|
0.130
|
|
|
4.1A-5A
|
0.120
|
|
|
5.1A-6A
|
0.100
|
|
|
6.1A-7A
|
0.075
|
|
|
7.1A-8A
|
0.035
|
|
|
8.1A-9A
|
0.020
|
|
|
9.1A-11A
|
0.015
|
|
|
11.1A-13A
|
0.010
|
|
|
13.1A-14A
|
0.010
|
|
|
14.1A-16A
|
0.008
|
|
|
16.1A-20A
|
0.007
|
|
|